Units Connected To The Rs485 Interface; External Fire Brigade Panels - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
6.2
6.2.1
AAFC Alarm Acknowledgement Facility Control.
box with an alarm indication LED and a non-latching switch
"Press to acknowledge false alarm". One AAFC per AAFC
zone and up to 50 AAFC zones can be used. The COM loop
address is set with an Address setting tool 3314 / 4414. See
also chapter "Alarm Acknowledgement Facility", page 135.

Units connected to the RS485 interface

Up to eight Ext. FBPs (1826 / 1828) and/or Alert Annunciation Units
(1735 / 1736) and/or Ext. Presentation Units (1728) can be connected
60
to the RS485 interface
printer. (Power supply at J1:13-14.)
Address and S/W mode settings
The display and the push buttons (in the unit respectively) are used to
set the address, which also can be changed via EBL128. The S/W
mode shall be set to xxxx – 1587 (xxxx = type number). See the
Technical Description for the unit respectively.
The first unit shall have the address 00, the second unit address 01 and
61
so on
. Follow the Address setting instructions in the Technical
Description for the unit respectively.
Via EBLWin can "Selective alarm presentation" be programmed, i.e.
you can select which alarms that shall be presented in each unit, see
the Technical Description for the unit respectively.

External Fire Brigade Panels

1826 External Fire Brigade Panel (ext. FBP). A light grey metal
housing (HxWxD, 288 x 400 x 95 mm) with a door. A key is
required to open the door, which has a Plexiglas ahead of the
FBP front. It has cable inlets on the top, bottom and back sides
and is intended to be wall mounted. Two compression glands
are attached.
LED indicators and push buttons on the front are like the
EBL128 FBP (upper black part of the front), see Figure 2, page
16. The front's designation texts are in Swedish. A neutral
front is available, where the designation texts, in any
language, are made separately and by production put into a
transparent "text slot" for the LED and push button respectively.
All or selected alarms will be presented in a display
(alphanumeric LCD, 2x40 characters), with back-light.
alarm text will also be presented together with each alarm, if
programmed in EBL128. Furthermore, at least 617 texts for
59
This unit is available on the Australian market only.
59
This unit is available on the Australian market only.
60
The RS485 transceiver 4552 is an option.
61
The connection order on the line is not dependent of the address.
EBL128 Planning Instructions V2.0.x
(J1:15-16) in EBL128. Max one 1826 with
53
59
The AAFC is a
An