Panasonic EBL128 Planning Instructions page 135

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
17.1.3.2
17.1.3.3
17.1.3.4
Alarm Acknowledgement Facility
Used in conjunction with the AAF Control that is available on the
Australian market only.
See also chapter "Alarm Acknowledgement Facility (AAF)", page
106.
Investigation period (IP) time: 3 min.
3 is default. 1-9 is possible.
Acknowledge period (AP) time: 60 sec.
60 is default. 10-120 is possible.
Disable routing equipment by door switch
Valid for the following control unit outputs for routing equipment:
Fire alarm (for Fire brigade tx)
Fault condition (for Fault tx)
 None (default): Door open in the C.U. or an ext. FBP will not
disable these outputs.
 Any control unit door: Door open in the C.U. will disable these
outputs.
 Any door: Door open in the C.U. or any ext. FBP will disable
these outputs.
In the display (or via menu H4/U1) is shown:
All
outputs
to
disabled by open door
Alarm reset method
One of the following alternatives shall be selected.
 All (default): All fire alarms will be reset simultaneously by
pressing the "Reset" button (on the c.i.e. front) once.
 Single: One fire alarm, i.e. the fire alarm shown in the control
unit display will be reset by pressing the "Reset" button once.
Any other fire alarm has to be reset the same way, one by one.
This function is a violation to the EN54-2 standard.
 Single With Automatic Disablement: Like "Single" reset but
with the Disablement function (see below) as well.
This function is a violation to the EN54-2 standard.
Disablement function: If an alarm point or zone is reset while it still is
in alarm state (e.g. smoke in a smoke detector or a manual call point
with a broken glass) this unit will be automatically disabled in order to
not activate a new fire alarm within 20 seconds. It will stay disabled
until re-enabled via menu H2/B6.
LED "Disablements" on the c.i.e. front is indicating one or more
disablements in the system.
133
EBL128 Planning Instructions V2.0.x
fire
alarm
routing
equip.