ABB PLC and drives integration using Modbus RTU
 
Hardware physical connection 
In the following chapter, physical connection of the hardware will be explained. 
Fieldbus grounding 
For  AC500,  which  has  opto‐isolated  COM  interfaces,  it  is  recommended  not  to  connect  the  ground.  For  AC500‐
eCo,  where  the  COM  interfaces  are  not  opto‐isolated,  it  is  recommended  to  connect  the  ground  at  one  place, 
typically in the bus master. For connection examples, see chapter "Installation examples". 
Fieldbus shield 
The shield should always be connected in a Modbus RTU line. The purpose of the shield is to protect against EMC 
disturbances and reflection on the bus line. For connection examples, see chapter "Installation examples". 
End termination 
Purpose: To avoid signal reflections. 
Resistor size: 120 Ohms, ¼ W. 
Where to connect: One resistor in each end of the bus line (first and last node). 
Pull up/pull down resistors 
Purpose: To keep a defined high level on the bus while there is no data exchange. 
Resistor  size:  Depends  on  bus  master  (COM)  voltage  level.  470  Ω  for  AC500 (5  V  output)  and  270  Ω  for 
AC500‐eCo (3.3 V output). 
Where to connect: Activate pull‐up and the pull‐down resistors, but only once on every bus line, at the bus 
master. 
Modbus RTU 
‐ 6 ‐ 
 
 