ABB PLC and drives integration using Modbus RTU
 
 
Set function block inputs according to: 
EN = TRUE (1) → The block will always be enabled. 
PRIO = Left unconnected. 
NVAR = Number of parameters to be read (2) → 2 parameters will be read in this example. 
PRM_NUM = Start address of parameters to be read (3) → parameters 12.02 and 12.03 will be read in this 
example. 
DATA  is  connected  via  an  "ADR"  block  to  a  new  variable  (4).  Press  the  "..."  button  (5)  and  choose  type 
"ARRAY" (6), set Start index to 1 and End index to the number of values to be read, 2 in this example (7). 
Set type to "INT" (8) and press "OK". 
DRIVE_DATA = The same variable that is connected to "ACS_COM_MOD_RTU" → "DRIVE_DATA" (9). 
 
 
Modbus RTU 
 
‐ 39 ‐ 
 
 
PLC and drives integration  
 