Quickstart Guide
 
ABB PLC and drives integration using Modbus RTU
 
 
Example ­ Write drive data with "ACS_MOD_WRITE_N_PRM" 
Values are written to Modbus register addresses according to user choice. No additional parameter settings in the 
drive are necessary. 
Create a new network in the same program (POU) and add the block "ACS_MOD_WRITE_N_PRM" (1). 
Set function block inputs according to: 
EN is connected to an "execute" variable of type "BOOL" (1). At rising edge the variable is written once. 
PRIO = Left unconnected. 
NVAR = Number of parameters to write (3) → 2 parameters will be written in this example. 
PRM_NUM = Start address of parameters to be written (4) → parameters 12.02 and 12.03 will be written 
in this example. 
DATA  is  connected  via  an "ADR"  block  to  a  new  variable  (5)  of  type  "ARRAY  [1..X]  OF  INT"  according  to 
instructions for the "ACS_MOD_READ_N_PRM" block. 
DRIVE_DATA = The same variable that is connected to "ACS_COM_MOD_RTU" → "DRIVE_DATA" (6). 
 
 
Modbus RTU 
 
‐ 41 ‐ 
 
 
 