Batteries

PowerValue can be configured with matching battery cabinets to satisfy extended runtime demands. Easily accessible, and
replaceable batteries increase availability and reduce Mean Time to Repair (MTTR).
The new battery cabinet is mechanically identical to the previous version but is can host double amount of batteries with
flexible configuration: double autonomy in the same footprint.

Battery autonomy

Battery cabinet configuration
A*
B**
UPS Internal Batteries
10 kVA
-
10 kVA S
-
10 kVA B
29 / 12 / 6 / 4
10 kVA B2
69 / 30 / 18 / 12
20 kVA
-
20 kVA S
-
20 kVA B
29 / 12 / 6 / 4
in minutes at 25 / 50 / 75 / 100% load
Given runtimes are estimates and valid at 20 degrees Celsius.
Actual runtime of the system will depend, among many variables, on the age of the batteries and environmental conditions
PowerValue 11/31 T Technical Specifications
Battery configuration
2 x 24 x 9 Ah
4 x 24 x 9 Ah
UPS + A*
69 / 30 / 18 / 12
-
109 / 49 / 29 / 21
151 / 69 / 42 / 30
29 / 12 / 6 / 4
-
69 / 29 / 18 / 12
UPS + B**
151 / 69 / 42 / 30
151 / 69 / 42 / 30
208 / 87 / 55 / 39
262 / 109 / 69 / 49
69 / 29 / 18 / 12
69 / 29 / 18 / 12
69 / 49 / 29 / 21
Page 4
UPS + A* + B**
UPS + 2B**
262 / 109 / 69 / 49
380 / 151 / 96 / 69
262 / 109 / 69 / 49
380 / 151 / 93 / 69
302 / 130 / 82 / 58
442 / 176 / 109 / 79
380 / 151 / 93 / 69
651 / 208 / 122 / 87
69 / 49 / 29 / 21
151 / 69 / 42 / 29
69 / 49 / 29 / 21
151 / 69 / 42 / 29
151 / 69 / 42 / 29
208 / 97 / 55 / 39