Huawei PDU8000-0125DCV8-BXA001 User Manual page 43

Battery circuit breaker box
Table of Contents

Advertisement

PDU8000-(0125, 0250, 0400, 0630, 0800)
DCV8-BXA001 Battery Circuit Breaker Box
User Manual
Step 2 Set MUE05A connection to Enable and then set both BCB connection [OL] and Battery
breaker [STA] to Enable.
Figure 4-2 BCB setting
----End
UPS New WebUI
Step 1 Log in to the WebUI and choose Monitoring > UPS system > Running Parameter > Dry
contact setting.
Step 2 Set Mue05a connection to Enable and then set both BCB connection and Battery breaker
to Enable.
Issue 03 (2019-05-20)
The preset passwords for admin and operator on the WebUI are both Changeme.
Copyright © Huawei Technologies Co., Ltd.
4 Setting Parameters
38

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents