Setting Parameters - Huawei PDU8000-0125DCV8-BXA001 User Manual

Battery circuit breaker box
Table of Contents

Advertisement

PDU8000-(0125, 0250, 0400, 0630, 0800)
DCV8-BXA001 Battery Circuit Breaker Box
User Manual
UPS LCD
Step 1 Choose System Info > Settings > Dry Contacts.
Step 2 Set MUE05A connection to Enable and then set both BCB connection [OL] and Battery
breaker [STA] to Enable.
Figure 4-1 BCB setting
----End
UPS WebUI
Step 1 Log in to the WebUI and choose Monitoring > Param. Settings > Dry Contacts.
Issue 03 (2019-05-20)
If you have not logged in, enter a user name and password (the preset passwords for admin and operator
are both 000001), and tap
The preset passwords for admin and operator on the WebUI are both Changeme.
Copyright © Huawei Technologies Co., Ltd.
4

Setting Parameters

on the login screen displayed.
4 Setting Parameters
37