Battery circuit breaker box
Table of Contents

Advertisement

PDU8000-(0125, 0250, 0400, 0630, 0800)
DCV8-BXA001 Battery Circuit Breaker Box
User Manual
Number of
Terminal
Terminals and
Hole Diameter
UPS–
2 x M16
(through-hole)
BAT +
2 x M16
(through-hole)
BAT N
2 x M16
(through-hole)
BAT–
2 x M16
(through-hole)
PE
1 x M16
(through-hole)
Table 3-6 Torque for securing bolts
Bolt Specifications
M6
M8
M10
M12
M16

3.2.4 Cable Connection Precautions

Issue 03 (2019-05-20)
Recommended
Cable
Specifications
1 x (2 x 185 mm
1 x (2 x 185 mm
1 x (2 x 185 mm
1 x (2 x 185 mm
2
1 x 185 mm
The recommended cable specifications are for reference only. Prepare cables based on site requirements.
Copyright © Huawei Technologies Co., Ltd.
Recommended
Wiring
Terminal
2
)
185-M16
2
)
185-M16
2
)
185-M16
2
)
185-M16
185-M16
Torque
5 N· m
13 N· m
27 N· m
47 N· m
120 N· m
Recommende
Recommended
d Bolt
Cable Color
Specifications
2 x (M16 x 60)
Black
2 x (M16 x 60)
Red
2 x (M16 x 60)
Blue
2 x (M16 x 60)
Black
M16 x 50
Green-and-yello
w