(104 °F) and air temperature of 45 °C (113 °F).
I
Maximum output (DC) current. Available for 10 s at start, otherwise as long as allowed by module
max
temperature.
S
Nominal apparent (AC) power
n
I
Maximum input (AC) current
max
P
Nominal output (DC) power
n
Light-overload use (50% overload capability) ratings
P
Typical power in heavy-duty use
I
Continuous current. 50% overload is allowed for one minute every 5 minutes.
Hd
Ld
P
Output power in light-overload use
Note 1: The ratings apply at an ambient air temperature of 45 °C (113 °F) and a coolant temperature of 40 °C
Ld
(104 °F).
Heavy-duty use (50% overload capability) ratings
Note 2: To achieve the rated power given in the table, the rated current must be higher than or equal to the
I
Continuous current. 50% overload is allowed for one minute every 5 minutes.
Hd
rated current. For dimensioning, use DriveSize dimensioning tool available from ABB.
P
Output power in heavy-duty use
Hd

Derating

Derating

Ambient temperature derating

Ambient temperature derating
In the temperature range +45...55 °C (+113...131 °F), the rated output current is derated
In the temperature range +45...55 °C (+113...131 °F), the rated output current is derated
by 0.5 percentage points for every added 1 °C (1.8 °F). The output current can be
by 0.5 percentage points for every added 1 °C (1.8 °F). The output current can be calculated
calculated by multiplying the current given in the rating table by the derating factor (k):
by multiplying the current given in the rating table by the derating factor (k):
k
1.00
0.95
0.90
+45 °C
+113 °F

Altitude derating

At altitudes from 1000 to 4000 m (3281 to 13123 ft) above sea level, the output current
derating is 1 percentage point for every added 100 m (328 ft). For example, the derating
factor for 1500 m (4921 ft) is 0.95.
For a more accurate derating, use the DriveSize PC tool.

Coolant temperature derating

See section
Temperature limits (page

Antifreeze content derating

See section
Temperature limits (page

Switching frequency derating

Switching frequencies other than default can require output current derating. Contact ABB
for more information.
ACS880-304LC ACS880-104LC_ambient temp dera
T
+55 °C
+131 °F
114).