The X485 Connector; Safe Torque Off (Xsto, Xsto Out); Fso-Xx Safety Functions Module Connection (X12); Sdhc Memory Card Slot - ABB ACS880-207LC Hardware Manual

Igbt supply units
Hide thumbs Also See for ACS880-207LC:
Table of Contents

Advertisement

58 Control units of the drive
BCU-x2
Termination ON

The X485 connector

The X485 provides a connection for optional CIO-01 I/O module. The following diagram
shows the wiring for the CIO module.
BCU
X485
B
A
BGND
SHIELD

Safe torque off (XSTO, XSTO OUT)

Note:
The XSTO input only acts as a true Safe torque off input on the inverter control unit.
De-energizing the IN1 and/or IN2 terminals of other units (supply, DC/DC converter, or brake
unit) will stop the unit but not constitute a true safety function.

FSO-xx safety functions module connection (X12)

See the user manual of the FSO-xx module. Note that the FSO-xx safety functions module
is not in use in supply (or DC/DC converter or brake) units.

SDHC memory card slot

The BCU-x2 has an on-board data logger that collects real-time data from the power modules
to help fault tracing and analysis. The data is stored onto the SDHC memory card inserted
into the SD CARD slot and can be analyzed by ABB service personnel.
Termination OFF
CIO
X485
B
A
GND
SHIELD
Termination ON
CIO
X485
B
A
GND
SHIELD