Powering The Heating And Lighting Equipment (Options +G300 And +G301); Connection Diagram - ABB ACS880-207LC Hardware Manual

Igbt supply units
Hide thumbs Also See for ACS880-207LC:
Table of Contents

Advertisement

50 Electrical installation
Powering the heating and lighting equipment (options
+G300 and +G301)
See the circuit diagrams delivered with the supply unit. Cabinet heaters and/or lighting (230
or 115 V AC, options +G300/+G301) are to be supplied from external power sources.
Connect the external power supply wires for the cabinet heater and lighting to terminal block
X22 at the mounting plate.

Connection diagram

External heating voltage supply
Q95
PE
PE
1
2
L1
3
4
N
5
6
X22
47
48
X22:47
Internal wiring of the cabinet heating: heat-
ing supply off/fault = contact open
X22:48
PE
L1
N
Q95
F95
X22:49
X22:50
External lighting voltage supply
Q130
PE
1
2
3
4
5
6
X22
49
Q130
50
Internal wiring of the cabinet lighting: light-
ing supply off/fault = contact open
F130