INSPECTION AND SERVICE
To Clean the Burner
1.
~
Remove cover panel (A) by removing the
screws (B).
~
Check that the boiler is completely isolat-
ed from the gas supply.
2.
~
Remove the clips (C) and unscrew the
two bolts (D).
~
Unscrew and remove the two hexagon
screws (E) securing the fan.
~Slacken
fully the rear securing bolt (F).
~
Remove the burner cover plate (G).
3.
~
Remove the burner (H) and clean compo-
nents. Do not use a wire brush.
To Check the Diaphragm
in Burner Cover
4.
~
Carefully withdraw diaphragm
(J)
from fan
intake tube and check for soiling and splits.
~
Carefully refit diaphragm
(J)
the correct
way round into the fan intake tube.
Note: The flaps of the diaphragm
(J)
must
open upwards.
~
Re-assemble burner in reverse order using
a new seal (K).
~Adjust
gas/air ratio. Refer to section
"Setting the gas/air ratio".
To Clean the Condensate Trap
5.1
~
Pull condensate pipe out of the adapter.
5.2~
Remove trap from boiler.
~
Clean trap and check that the connection
to the heat exchanger is clear.
~
Fill the condensate trap with approxi-
mately 1/4 litre of water and refit in reverse
order.