Bosch Worcester Greenstar CDi Conventional Series Instruction Manual page 24

Wall hung rsf gas-fired condensing regular boiler for open vented and sealed central heating systems and indirect domestic hot water
Table of Contents

Advertisement

Ql
m~q
t
Clamp
I
2380mm
I
w
tJ
tJ
I
I
!t
I
t
I
t
I
t
52 mm
960 mm
734mm
634mm
Turret
Extension
Cut Length
Standard Flue
I
Required Length
1
~----------------~
I
I
c::::::::::::::::::::::-1
.
~
Seal
I
94 mm
I
I
94 mm
I
....
..
' . .
..
'
I
I
I
I
m.--'----T:
---------r-'-------,--1 - -
~0~
I
6 720 611 927-05.1
0
~p
I
I
!llil?
FLUE
INSTALLATION
MEASURING THE FLUE (Extension Flue Kits):
ONLY CUT EXTENDED FLUE LENGTHS
~
As with the Standard Flue measure from the
outside wall to the centre line of the flue tur-
ret (length L).
~
Subtract the usable length of the standard
flue (634 mm) from length
L.
~
Subtract the usable length of the turret
(52 mm) from length
L.
~
Subtract 960 mm for each full length exten-
sian from the figure.
~
Cut one of the extensions to the remainder.
~
Cut both tubes square taking care not to distort
the tubes.
~
Remove any burrs.
EXAMPLE:
Length L
2380 mm
Subtract Standard Flue
-634 mm
Subtract Turret
-52mm
Subtract Full Extension
-960 mm
Cut Length
734mm
NOTE: Where extensions are reduced, cut
length which
DOES NOT
contain the seal.
ADDITION OF FLUE BENDS:
When flue bends are being used an allowance
of 94 mm per bend must be allowed from the
centre line of the bend. In the example shown
using a flue extension (960 mm) with 2 bends
will achieve a total length of 1148 mm.
FLUE INSTALLATION
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER BOSCH GREENSTAR 30CDI/40CDI Coc,ectlocal
~ORCESTER
6 720 614 556a (2007/07)
Bosch Group