Mitsubishi Electric Melsec QJ71LP21 Reference Manual page 434

Q corresponding melsecnet/h network system
Hide thumbs Also See for Melsec QJ71LP21:
Table of Contents

Advertisement

8
TROUBLESHOOTING
8 - 50
Item
CRC
During received data code check errors: Illuminated
1)-a: Forward loop side, 1)-b: Reverse loop side
OVER
During delayed received data processing errors: Illuminated
1)-a: Forward loop side, 1)-b: Reverse loop side
AB.IF.
When errors are triggered owing to values other than the stipulated "1" are received
consecutively, and when errors are triggered owing to the length of the received data being too
short: Illuminated
1)-a: Forward loop side, 1)-b: Reverse loop side
TIME
When errors are triggered owing to the data link monitoring timer being activated: Illuminated
1)-a: Forward loop side, 1)-b: Reverse loop side
DATA
When errors are triggered owing to abnormal data exceeding 2kbytes has been received:
Illuminated
1)-a: Forward loop side, 1)-b: Reverse loop side
UNDER
When errors are triggered owing to the internal processing of transmission data not being
completed within the specified period of time: Illuminated
1)-a: Forward loop side, 1)-b: Reverse loop side
LOOP
When errors are triggered owing abnormalities on the loop: Illuminated
1)-a: Forward loop side, 1)-b: Reverse loop side
2)
H/W switch information
Displays the switch information for the network module.
2)-a: Displays the switch settings for the H/W mounted on the network
module.
Item
STx10
Position 10 of the station number setting switch
STx1
Position 1 of the station number setting switch
MODE
Mode setting switch
2)-b: Displays the switch information actually set up on the network module.
Item
NETNO.
Network number setting
GRPNO.
Group number setting
STNO.
Station number setting
MODE
Operation mode setting
BAUD
Communication speed
CONFIG
Station type, controlled station operations
during recovery, transmission mode settings
Description
Description
Description
MELSEC-Q
Display range
0 to 239
0 to 9
1 to 64
0: On-line
7: Self loop-back test
8: Internal self loop-back test
9: Hardware test
Optical loop
Coaxial bus
0: 10 Mbps
0: 10 Mbps
1: 25 Mbps
b15
b8 b7
b5
All "0"
Empty
Controlled station
operations
0: Switched
1: Not switched
Transmission mode
0: On-line mode (start)
1: Debug mode (stop)
Twisted bus
0: 156Kbps
1: 312Kbps
2: 625Kbps
3: 1.25Mbps
4: 2.5Mbps
5: 5Mbps
6: 10Mbps
b0
Station type
0: Normal station
1: Controlled station
8 - 50