APPLICATION FUNCTIONS
Request data (All set by the user)
Device
Item
(S2)+0
Request type
(S2)+1
Sub-request type
(S2)+2
Operation mode
(S2)+3
Clear mode
Response data (All set by the system)
Device
Item
(D1)+0
Request type
(D1)+1
Sub-request type
7: When "all stations or a group (FF
7 - 78
2) Request data (S2)/response data (D1) at remote RUN/STOP
0010
: When station No. is specified in (S1)+5
H
0030
: When all stations or a group is specified in (S1)+5
H
0001
: Remote RUN
H
0002
: Remote STOP
H
Specify whether to forcibly execute remote RUN/STOP or not.
The forced execution is a function that forces a station which has stopped by
remote STOP to RUN remotely from another station.
• For remote RUN
0001
: No forced execution
H
0003
: Forced execution
H
• For remote STOP
0003
(Fixed)
H
Specify the CPU module device status for the case of remote RUN.
0000
: Do not clear (Note that the local devices are cleared.)
H
0001
: Clear (excluding the latch range)
H
0002
: Clear (including the latch range)
H
Clear mode ((S2)+3) allows specification of the CPU module device clear
(initialization) process at the start of CPU module operation activated by remote
RUN.
The CPU module will perform the specified clear processing, and then it will run
according to the setting that can be confirmed by [PLC parameters] - [PLC file] -
[Initial Device value] in GX Developer.
0090
: When station No. is specified in (S1)+5
H
0001
: Remote RUN
H
0002
: Remote STOP
H
or 81
to A0
)" is specified in Target station No. ((S1)+5), no response data will be stored.
H
H
H
POINT
(1)
Remote RUN/STOP is available when the RUN/STOP switch of the target
station CPU is set to "RUN".
(2)
Remote RUN/STOP is not executable when system protect is applied to the
target station CPU module.
(3)
When the target station CPU has been already in remote STOP/PAUSE state
by a request from another station, it cannot enter RUN mode if Mode ((S2+2)
is "No forced execution (0001
(4)
If the target station CPU module, for which remote STOP was performed, is
reset, the remote STOP information is erased.
Setting data
7
Setting data
)".
H
MELSEC-Q
Remote
Remote
RUN
STOP
: Set
: Not set
Remote
Remote
RUN
STOP
: Stored
: Not stored
7 - 78