7 APPLICATION FUNCTIONS
Control system
(system A)
Redundant
Normal
CPU
station
Q25H
Control
CPU
station
7 - 138
(1) Configuring a MELSECNET/H network including a redundant
system
When configuring a MELSECNET/H network including a redundant system or
when connecting a redundant system to an existing MELSECNET/H, follow the
restrictions shown below.
(a)
When configuring a new MELSECNET/H network including a redundant
system
To configure a new MELSECNET/H network including a redundant system,
use the following network modules and GX Developer.
Standby system
(system B)
Redundant
CPU
Tracking cable
Q25H
[Setting of the redundant CPUs]
1) Install a network module of function version D or
later to each of the redundant CPUs.
2) Set the parameters for the redundant system using
GX Developer of version 8.18U or later.
Normal
station
Normal
CPU
station
[Setting when using a CPU other than the
redundant CPUs as the control station]
1) Use a network module of function version D or later
for the control station.
2) Set the parameters for the control station using GX
Developer of version 8.18U or later.
MELSEC-Q