Appendix 1.6 EMC Countermeasure Parts

Appendix 1.6.1 Shield Clamp Fitting

The effect can be improved by directly connecting the cable's shield sheath to the grounding plate as shown
below.
Install the grounding plate near the outlet (within 10cm) of each panel, and press against the grounding plate
with the clamp fitting. If the cables are thin, several can be bundled and clamped together.
To provide sufficient frame ground, install the grounding plate directly on the cabinet or connect with a
grounding wire.

Appendix 1.6.2 Ferrite Core

The ferrite core is mounted integrally with the plastic case.
This can be installed with one touch without cutting the interface cable or power supply cable.
This ferrite core is effective against common mode noise, allowing measures against noise without affecting
the quality of the signal.
Shape and dimensions
ZCAT type
ZCAT-C type
Clamp fitting
(Fitting A,B)
Clamp section drawing
ZCAT-A, ZCAT-AP type
ZCAT-D type
C70 Connection Manual
Appendix 1.6 EMC Countermeasure Parts
Peel off the cable sheath at the
clamp section.
Cable
Grounding
plate
Cable
Shield
sheath
ZCAT-B type
89