Aux Relay 1/2 Config - GE MOTOR MANAGER 2 Instruction Manual

Hide thumbs Also See for MOTOR MANAGER 2:
Table of Contents

Advertisement

4 SETPOINTS
PATH: SETPOINTS MMMM S4 CONTROL MM AUX 1/2 RELAY CONFIG
The MM2 has two auxiliary programmable output relays. These two outputs can be assigned any of
the functions listed below. Once a function has been assigned to one of the auxiliary relays it cannot
be assigned to the other with the exception of the SERIAL CONTROL function which can be set to
both auxiliary relays.
The setpoints listed under the AUX RELAY 2 CONFIG page operate in the same manner as
the setpoints shown for AUX RELAY 1 CONFIG.
NOTE
AUX RELAY 1 FUNCTION:
SERIAL CONTROL
AUX RELAY 1 DELAY
5 s
AUX RELAY 1 PRE
START DELAY: 5 s
AUX RELAY 1 POST
START DELAY: OFF s
ENERGIZE ON MOTOR
START DELAY: 5 s
DE-ENERGIZE ON MOTOR
STOP DELAY: 5 s
GE Power Management
Range: SERIAL CONTROL, TRIPS, ALARMS, PRE CONTACTOR A,
POST CONTACTOR A, POST CONTACTOR B, MOTOR AVAILABLE-
MAN, LOAD INCREASE ALARM, UNDERCURRENT TRIP, UNDER-
POWER TRIP, KEYPAD RESET, INTERLOCK 1 to INTERLOCK 10,
AUTO MODE, MOTOR RUNNING, GROUND FAULT TRIP, WYE-
DELTA CLS TRANS, AUTOTRANSFORMER 2S, NOT USED, PRE
CONTACTOR B, SEGREGATED G/F ALARM, THERMAL CAPACITY
ALARM, MOTOR AVAILABLE AUTO, MOTOR AVAILABLE, OVER-
LOAD, SOFT STARTER BYPASS
The dual form "C" AUX Relay 1 can be configured to activate on various
conditions as described below.
Range: 0 to 125 sec.; Step: 1
Provides a delayed energization of AUX Relay 1 when POST CONTACTOR
A or POST CONTACTOR B is selected as the AUX RELAY 1 FUNCTION.
Range: 0 to 900 sec.; Step: 1
Determines how long the AUX Relay 1 will energize before energizing
Contactor A. When set to 0, both AUX Relay 1 and Contactor A will
energize at the same time.
Range: 0 to 125 sec. or OFF; Step: 1
Determines how long AUX 1 remains energized after Contactor A
closes. When set to 0, AUX 1 de-energizes as soon as Contactor A
closes. When set to OFF, AUX 1 remains energized until Contactor A
opens.
Range: 0 to 125 sec.; Step: 1
Provides a delayed energization of the AUX Relay 1 when MOTOR RUN-
NING is selected as the AUX RELAY 1 FUNCTION. The AUX Relay 1 ener-
gizes after this time delay on the occurrence of a motor start.
Range: 0 to 125 sec.; Step: 1
Provides a delayed de-energization of the AUX Relay 1 when MOTOR
RUNNING is selected as the AUX RELAY 1 FUNCTION. The AUX Relay 1 will
de-energize after this time delay on the occurrence of a motor stop.
MM2 Motor Manager 2
4.5 S4 CONTROL

4.5.3 AUX RELAY 1/2 CONFIG

4
4-29