8 MM2PC
SOFTWARE
8.5 CHASSIS MOUNT UNITS
MM2 chassis mount units no longer support automatic baud rate linking. The default communication
settings are 9600 baud, 8 data bits, one stop bit, no parity. It is necessary to initially communicate
with these settings and change them one at a time. After each change the master must be changed
to match the communication setting change in the MM2.
Assume your system communicates at 19200 baud and even parity.
®
1. Use MM2PC
to establish communications with the chassis mount MM2 at 9600 baud and no
parity.
2. Select the Communication > Set Slave Address menu item and follow the on screen instruc-
tions to store the communication address of the MM2. When completed, select OK to exit.
GE Power Management
8.5.2 SETTING THE BAUD RATE AND PARITY
MM2 Motor Manager 2
8.5 CHASSIS MOUNT UNITS
8.5.1 DESCRIPTION