AF-650 GP 3-phase
[kW] / [HP]
0.25 / 0.33
0.37 / 0.5
0.75 / 1
1.5 / 2
2.2 / 3
3.7 / 5
5.5 / 7.5
7.5 / 10
11 / 15
15 / 20
18.5 / 25
22 / 30
30 / 40
37 / 50
Table 9.1 200–240V. IP20 / Open Chassis
AF-650 GP 3-phase
[kW] / [HP]
0.25 / 0.33
0.37 / 0.5
0.75 / 1
1.5 / 2
2.2 / 3
3.7 / 5
5.5 / 7.5
7.5 / 10
11 / 15
15 / 20
18.5 / 25
22 / 30
30 / 40
37 / 50
Table 9.2 200–240V. IP55 / Nema 12 and IP66 / Nema 4
AF-650 GP Quick Guide
Recommended fuse size
gG-16
gG-20
gG-50
gG-80
gG-125
aR-160
aR-200
aR-250
Recommended fuse size
gG-20
gG-63
gG-80
gG-125
aR-160
aR-200
aR-250
DET-759A
Recommended max fuse
gG-25
gG-32
gG-63
gG-125
gG-150
aR-160
aR-200
aR-250
Recommended max fuse
gG-32
gG-80
gG-100
gG-160
aR-160
aR-200
aR-250