GE AF-650 GP Design Manual page 60

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Mains Supply 3 x 380 - 480 VAC
AF-650 GP
Heavy Duty/Light Duty*
Typical Shaft output at 400 V
[kW]
Typical Shaft output at 460 V
[HP]
Typical Shaft output at 480 V
[kW]
IP21/Nema 1 Drive Type
IP54/Nema 12 Drive Type
IP00 Open Chassis Drive
Type
Output current
Continuous
(at 400 V) [A]
Intermittent (60 sec over-
load)
(at 400 V) [A]
Continuous
(at 460/ 480 V) [A]
Intermittent (60 sec over-
load)
(at 460/ 480 V) [A]
Continuous KVA
(at 400 V) [KVA]
Continuous KVA
(at 460 V) [KVA]
Continuous KVA
(at 480 V) [KVA]
Max. input current
Continuous
(at 400 V ) [A]
Continuous
(at 460/ 480 V) [A]
Max. cable size, mains, mo-
tor and load share [mm
2)
(AWG
)]
Max. cable size, brake [mm
(AWG
2)
)
Max. external mains fuses
[A]
1
Estimated power loss
at 400 V [W]
Estimated power loss
at 460 V [W]
Weight,
Unit Size IP21, IP 54 [kg]
Weight,
Unit Size IP00 [kg]
4)
Efficiency
Output frequency
Heatsink overtemp. trip
Power card ambient trip
* Heavy Duty = 160% torque during 60 s, Light Duty = 110% torque during 60 s
350 HP
HD
LD
250
315
350
450
315
355
51
51
52
480
600
720
660
443
540
665
594
333
416
353
430
384
468
472
590
436
531
4x240
2
(4x500 mcm)
2
2 x 185
(2 x 350 mcm)
700
5164
6790
4)
4822
6082
263
221
450 HP
500 HP
HD
LD
HD
LD
315
355
355
400
450
500
500
600
355
400
400
500
51
51
51
51
52
52
600
658
658
745
900
724
987
820
540
590
590
678
810
649
885
746
416
456
456
516
430
470
470
540
468
511
511
587
590
647
647
733
531
580
580
667
4x240
4x240
(4x500 mcm)
(4x500 mcm)
2 x 185
2 x 185
(2 x 350 mcm)
(2 x 350 mcm)
900
900
6960
7701
7691
8879
6345
6953
6944
8089
270
272
234
236
0.98
0 - 600 Hz
95 °C
68 °C
AF-650 GP Design Guide
550 HP
HD
LD
400
450
550
600
500
530
51
51
52
695
800
4
1043
880
678
730
1017
803
482
554
540
582
587
632
684
787
667
718
4x240
(4x500 mcm)
2 x 185
(2 x 350 mcm)
900
8178
9670
8085
8803
313
277
59