12, 13, 23
1)
IMPORTANT ! The label MUST be placed on the Keypad frame as shown (UL approved).
Warning Dual supply
How to add the OPCRLY Relay Option Module:
•
The power to the frequency converter must be disconnected.
•
The power to the live part connections on relay terminals must be disconnected.
•
Remove the Keypad, the terminal cover and the Keypad fixture from the frequency converter.
•
Fit the OPCRLY Relay Option Module in slot B.
•
Connect the control cables and fasten the cables with the enclosed cable strips.
•
Make sure the length of the stripped wire is correct (see the following drawing).
•
Do not mix live parts (high voltage) with control signals (PELV).
•
Fit the enlarged Keypad fixture and enlarged terminal cover.
•
Replace the Keypad.
•
Connect power to the frequency converter.
•
Select the relay functions in par. E-24 Function Relay [6-8], par. E-26 On Delay, Relay [6-8] and par. E-27 Off Delay, Relay [6-8].
NB!
Array [6] is relay 7, array [7] is relay 8, and array [8] is relay 9
AF-650 GP Design Guide
15, 21, 22, 24, 31, 32, 33, 34
9
175