GE AF-650 GP Design Manual page 205

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

AF-650 GP Design Guide
Bit 02, Coasting/Enable
When bit 02 = "0", bit 00, 01 or 02 of the Control word is "0" (OFF 1, OFF 2 or OFF 3 or coasting) - or the frequency converter is switched off (trip).
When bit 02 = "1", bit 00, 01 or 02 of the Control word is "1"; the frequency converter has not tripped.
Bit 03, No error/Trip
When bit 03 = "0", no error condition of the frequency converter exists.
When bit 03 = "1", the frequency converter has tripped and requires a reset signal before it can start.
Bit 04, ON 2/OFF 2
When bit 01 of the Control word is "0", then bit 04 = "0".
When bit 01 of the Control word is "1", then bit 04 = "1".
Bit 05, ON 3/OFF 3
When bit 02 of the Control word is "0", then bit 05 = "0".
When bit 02 of the Control word is "1", then bit 05 = "1".
Bit 06, Start possible/Start not possible
If PROFIdrive has been selected in par. O-10 Control Word Profile, bit 06 will be "1" after a switch-off acknowledgement, after activation of OFF2 or OFF3, and after
switching on the mains voltage. Start not possible will be reset, with bit 00 of the Control word being set to "0" and bit 01, 02 and 10 being set to "1".
Bit 07, No warning/Warning
Bit 07 = "0" means that there are no warnings.
Bit 07 = "1" means that a warning has occurred.
Bit 08, Speed ≠ reference / Speed = reference
When bit 08 = "0", the current speed of the motor deviates from the set speed reference value. This may occur, for example, when the speed is being changed
during start/stop through ramp up/down.
When bit 08 = "1", the current speed of the motor corresponds to the set speed reference value.
10
Bit 09, Local operation/Bus control
Bit 09 = "0" indicates that the frequency converter has been stopped by means of the stop button on the Keypad, or that [Linked to hand] or [Local] has been
selected in par. F-02 Operation Method.
When bit 09 = "1", the frequency converter can be controlled through the serial interface.
Bit 10, Out of frequency limit/Frequency limit OK
When bit 10 = "0", the output frequency is outside the limits set in par. H-72 Warning Speed Low and par. H-73 Warning Speed High. When bit 10 = "1", the output
frequency is within the indicated limits.
Bit 11, No operation/Operation
When bit 11 = "0", the motor does not turn.
When bit 11 = "1", the frequency converter has a start signal, or the output frequency is higher than 0 Hz.
Bit 12, Drive OK/Stopped, autostart
When bit 12 = "0", there is no temporary overloading of the inverter.
When bit 12 = "1", the inverter has stopped due to overloading. However, the frequency converter has not switched off (trip) and will start again after the overloading
has ended.
Bit 13, Voltage OK/Voltage exceeded
When bit 13 = "0", the voltage limits of the frequency converter are not exceeded.
When bit 13 = "1", the direct voltage in the intermediate circuit of the frequency converter is too low or too high.
Bit 14, Torque OK/Torque exceeded
When bit 14 = "0", the motor torque is below the limit selected in par. F-40 Torque Limiter (Driving) and par. F-41 Torque Limiter (Braking). When bit 14 = "1", the
limit selected in par. F-40 Torque Limiter (Driving) or par. F-41 Torque Limiter (Braking) is exceeded.