Table 7.2: For Unit Sizes 41, 42, 43, and 44, 380-480 V
AF-650 GP
Bussmann PN*
350 HP
170M4017
400 HP
170M6013
500 HP
170M6013
550 HP
170M6013
Table 7.3: For Unit Sizes 51 and 52, 380-480 V
AF-650 GP
Bussmann PN*
600 HP
170M7081
650 HP
170M7081
750 HP
170M7082
900 HP
170M7082
1000 HP
170M7083
1200 HP
170M7083
Table 7.4: Unit Sizes 61, 62, 63, and 64, 380-480 V
AF-650 GP
Bussmann PN*
600 HP
650 HP
750 HP
900 HP
1000 HP
1200 HP
Table 7.5: Unit Sizes 61, 62, 63, and 64, Inverter module DC Link Fuses, 380-480 V
*170M fuses from Bussmann shown use the -/80 visual indicator, -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and amperage may be
substituted for external use
**Any minimum 480 V UL listed fuse with associated current rating may be used to meet UL requirements.
525-690 V, unit sizes 4x, 5x and 6x
Bussmann
AF-650 GP
E125085
JFHR2
125 HP
170M3016
150 HP
170M3017
200 HP
170M3018
250 HP
170M4011
300 HP
170M4012
350 HP
170M4014
400 HP
170M5011
Table 7.6: Unit Size 41, 42, 43, and 44, 525-690 V