Bits 13/14, Set-up selection
Bits 13 and 14 are used to choose between the four parameter set-ups ac-
cording to the following table:
The function is only possible if Multi Set-up has been chosen in par. K-10 Active
Set-up. The selection in par. O-55 Set-up Select determines how bits 13 and
14 are linked with the corresponding function of the digital inputs. Changing
set-up while running is only possible if the set-ups have been linked in
par. K-12 This Set-up Linked to.
Bit 15, No function/Reverse
Bit 15 = "0" causes no reversing.
Bit 15 = "1" causes reversing.
Note: In the factory setting reversing is set to digital in par. O-54 Reversing Select.
NB!
Bit 15 causes reversing only when Ser. communication, Logic or or Logic and is selected.
10.10.6 Status Word according to PROFIdrive Profile (STW)
The Status word is used to notify a master (e.g. a PC) about the status of a
slave.
Explanation of the Status Bits
Bit 00, Control not ready/ready
When bit 00 = "0", bit 00, 01 or 02 of the Control word is "0" (OFF 1, OFF 2 or OFF 3) - or the frequency converter is switched off (trip).
When bit 00 = "1", the frequency converter control is ready, but there is not necessarily power supply to the unit present (in the event of external 24 V supply of
the control system).
Bit 01, Drive not ready/ready
Same significance as bit 00, however, there is a supply of the power unit. The frequency converter is ready when it receives the necessary start signals.
Set-up
Bit 13
1
0
2
1
3
0
4
1
Bit
Bit = 0
Bit = 1
00
Control not ready
Control ready
01
Drive not ready
Drive ready
02
Coasting
Enable
03
No error
Trip
04
OFF 2
ON 2
05
OFF 3
ON 3
06
Start possible
Start not possible
07
No warning
Warning
Speed ≠ reference
08
Speed = reference
09
Local operation
Bus control
10
Out of frequency limit
Frequency limit ok
11
No operation
In operation
12
Drive OK
Stopped, autostart
13
Voltage OK
Voltage exceeded
14
Torque OK
Torque exceeded
15
Timer OK
Timer exceeded
AF-650 GP Design Guide
Bit 14
0
0
1
1
10