8

Displays on the Module

8.1

Status / warning displays

LED
FG
FGI
Computer
booted
TEMP
STA
Read
Unit Description
from
DSS
A00
A-0-1000
Hz
A01
A-0-1001
Hz
A02
A-0-1002
A03
A-0-1003
A04
A-0-1004
A05
A-0-1005
A06
A-0-1006
A07
A-0-1007
kVA
A08
A-0-1008
kW
1070 066 028-101 (01.05) GB
Status
Axis enable external if
D 24 V at X06.3/4 (FG) present
Enable internal if
D 24 V at X06.3 (FG) present
D Central enable by VM present
D no faults
3-digit 7-segment display
Operating display:
D STA is present if:
– computer has been booted
– no faults
Temperature status:
D TEMP is present if:
Temperature of the heat sink or the mo-
tor (with active bimetal function) is within
the permitted range
D TEMP relay is closed
More operating data can be read from the 7-segment display. For operation,
refer to section 3.3.
Actual output frequency f
Setpoint output frequency
f
set
A
Total current
A
Active current
A
Reactive current
V
Motor voltage
V
Link voltage
Total power
Shaft output
Measures
If no display (temp. exceeded):
D Check air supply, fan
D Reduce clock frequency or load
D Select motor with higher rating
D Verify bimetal setting
Current motor frequency
act
Specified output frequency
rms value of the total current
rms value of the active current
rms value of the reactive current
rms value of the current motor voltage
Current value of the link voltage.
(Display = 350 V for voltage values x 350 V)
Current total power
Current mechanical shaft output of the motor
Displays on the Module
8–1