5.2

Commissioning

5.2.1

Subsequent optimization during operation

1070 066 028-101 (01.05) GB
D All parameters have been checked and all necessary adjustments have
been made according to Section 5.1.
D Set setpoint selection to '0'.
D Activate enable signal. The basic operating display is shown.
For a description, see Section 2.1.
D Carefully increase setpoint.
The motor speed must increase accordingly.
D If the motor has been properly connected, a positive setpoint will cause
the motor to rotate clockwise (when looking at the motor shaft).
D Slowly increase setpoint up to maximum value. Check the maximum
admissible speed for clockwise and counter-clockwise rotation.
The direction of rotation is changed by reversing the polarity of the
setpoint cables connected to X6.5 and X6.6.
During operation, the drive behavior can be further improved. When the
enable signal FG has been activated, the following parameters can be
subsequently optimized:
P09, P10
I x R compensation
P11
Acceleration time
P12
Braking time
P14
Keyboard setpoint
P22 – P24 Direct current braking
P32
Slip compensation
P33 – P36 Stalling warning
P37, P38
Frequency monitoring functions
P39 – P42 Analog outputs
P48, P49
2-step acceleration ramp
.
For safety reasons, some of these values can only be changed step by
step.
Commissioning
5–27