Operation With Zero-Speed Control - Bosch DM**8001 Series Parameter And Commissioning Manual

Frequency inverters (asm)
Table of Contents

Advertisement

Commissioning
5–28
5.2.2

Operation with zero-speed control

Zero-speed control may serve as a protective function which can also be
used if two identical motors are operated by one inverter.
For activating zero-speed control, activate parameter P20.
If the FG enable signal had been activated before, first cycle power to the
unit, then activate P20.
DANGER
Zero-speed control is guaranteed only if the motor is standing when
monitoring is switched on!
The following messages are output in connection with zero-speed control.
External enable
Motor status
signal FG
on
running or standing
(operation)
decelerating
off
standing
Messages
X34.3
FGI relay
n = 0
0 V
0 V
24 V
1070 066 028-101 (01.05) GB