Remote Communication Failure - ABB X Series G5 Startup Manual

Flow computers and remote controllers
Hide thumbs Also See for X Series G5:
Table of Contents

Advertisement

a.
Locate the COLDBOOT button (S9) and the RESET button (XFC S2
and XRC S6) on the electronic board.
b.
Press and hold the COLDBOOT button and at the same time
press and hold the RESET button for 10 seconds.
c.
The LCD displays "Loading Boot Loader".
d.
Verify the Power On sequence is completed.
e.
If the display moves through the startup screens and begins
cycling correctly, the COLDBOOT was successful.
f.
If the display does not begin cycling correctly or locks up on one
of the startup screens, contact technical support for additional
instructions.
IMPORTANT NOTE: To reach technical support, call the ABB Totalflow
main office, listed under
from the menu options.

Remote communication failure

IMPORTANT NOTE: Use COMM1 for remote communication.
Use the following list to eliminate possible remote communications issues
(in any order):
1.
Verify that the
Figure 13-1: XSeriesG5
actively running Totalflow Remote Protocol. Each flash identifies
the Listen Cycle time period.
a.
If the
i.
Set the port Listen Cycle to zero. The symbol should display
continuously.
ii.
Select Totalflow Remote Protocol in the configuration of
the port, see
iii.
Increase the cutoff voltage value specified in Station Setup
> Remote Comm Cutoff Voltage. This helps determine if
COMM1 is deactivated due to a drop in the voltage to the
device. The default is 11.9 Vdc. Use voltage values based on
the power mode used. Click Help in the Station Setup
screen for more details
2.
Verify that these are correct:
a.
The communication port wiring on the flow computer
b.
The communication port wiring on the radio
c.
All communication cables are intact and undamaged
Contact
symbol flashes in the A8 display position, see
annunciators. This indicates that the port is
symbol is not flashing:
10.1: Configure
2 1 0 60 01M NAA | XSER IE S G5 S TART UP G UI DE | 7 5
us: and select technical support
COMM1.