Error
Error details and causes
code
C0B2H
There is no sufficient space in the receive buffer or the
send buffer of the relay station or external station for the
MELSOFT connection, link dedicated instructions, or
SLMP. (Send  receive buffer full error)
C0B3H
A request that cannot be processed was issued from the
CPU module.
C0B6H
The channel specified by the dedicated instruction is out
of the range.
C0BAH
Since the close processing is in execution using the
CONCLOSE/CLOSE instruction, a send request cannot
be accepted.
C0C4H
The UINI instruction has been executed during
communications.
C0D0H
The specified data length of the link dedicated instruction
is incorrect.
C0D1H
The number of resends of the link dedicated instruction is
incorrect.
C0D3H
The number of relay stations to communicate with other
networks exceeds the allowable range.
C0D4H
The number of relay stations to communicate with other
networks exceeds the allowable range.
C0D5H
The number of retries of the link dedicated instruction is
incorrect.
C0D6H
The network number or station number of the link
dedicated instruction is incorrect.
C0D7H
Data were sent without the initial processing completed.
C0D8H
The number of specified blocks exceeded the range.
C0D9H
The specified subcommand of the SLMP message is
incorrect.
C0DAH
A response to the PING test could not be received within
the time of the communication time check.
C0DBH
The IP address and host name of the target module
where the PING test is execute are incorrect.
C0DEH
Data could not be received within the specified arrival
monitoring time.
C101H
A response could not be received from the DNS server.
Action
• Increase the request interval (execution interval) and
execute the operation.
• Do not access through one station using the
MELSOFT connection, link dedicated instruction, or
SLMP.
• Wait for a response to the previous request before
sending the next request.
• Correct the set value for "Timer Settings for Data
Communication" under "Application Settings" of the
Ethernet-equipped module.
• Correct the request details.
• Correct the network number or request destination
station number.
Correct the channel to a value within the allowable range
of each dedicated instruction.
Do no perform the send processing during the close
processing.
Execute the UINI instruction after closing all connections.
Correct the data length.
Correct the number of resends.
• Check if the specification (network number/station
number) for the communication destination is correct.
• Check that number of relay stations accessing to the
communication destination is 7 or less.
• Correct the settings in the Network station number <->
IP information for the stations between the own station
and the communication destination.
• Check if the specification (network number/station
number) for the communication destination is correct.
• Check that number of relay stations accessing to the
communication destination is 7 or less.
• Correct the settings in the Network station number <->
IP information for the stations between the own station
and the communication destination.
Correct the number of retries.
Check if the specification (network number/station
number) for the communication destination is correct.
After normal completion of the initial processing, perform
the communications with the external device.
Correct the number of blocks.
Correct the subcommand.
• Correct the IP address and host name of the target
module where the PING test is executed.
• Check that the initial processing of the Ethernet-
equipped module where the PING test is executed is
completed successfully.
Correct the IP address and host name of the target
module where the PING test is executed.
• Correct the specified arrival monitoring time.
• Correct the channel of the link dedicated instruction.
• Check if the sending station and relay station are
operating normally.
• Check the address of the DNS server.
• Check that the data communications with the DNS
server is possible by using the Ping command.
• Check that the own station IP address and the DNS
server IP address are in the same class. (If not, check
the router setting.)
Detailed information
3 TROUBLESHOOTING
317
3.5 List of Error Codes