Communications using the predefined protocol cannot be performed.

When communications using the predefined protocol cannot be performed, check the following items and take action.
Check item
Is the IP address setting of the external device correct?
Has the connection with the external device been opened? (Check 'Open
completion signal' (Un\G1900000 to Un\G1900007)
Has the send/receive processing (dedicated instruction) for the
communications using the predefined protocol been executed properly?
Is the appropriate protocol used for the external device in the predefined
protocol settings and program?
Is the communication method of the connection used for communication with
the external device is set to an item other than "Predefined Protocol" in the
"External Device Configuration" window of "Basic Settings"?
Is 'Predefined protocol ready' (Un\G1901002.0) on?
If the above action does not solve the problem, perform the module communication test to check for hardware failure. (
Page 284 Module communication test)
*1 The buffer memory address is for when the network type of the RJ71EN71 or the RnENCPU (network part) is set to "Ethernet" and the
P1 connector is used.
When using the P2 connector or the CPU module (built-in Ethernet port part), or setting the network type to "Q Compatible Ethernet",
refer to the following.
Page 336 Buffer Memory
*2 If the connection of only the external device is closed due to cable disconnection, personal computer restart, or other reasons, reopen
the connection using the same port used before the error occurred. The E71 does not close a connection if it receives an Active open
request again from the external device with a different IP address or a port number.
*3 The module communication test cannot be performed for the CPU module (built-in Ethernet port part). Perform the troubleshooting of
the CPU module and check for hardware failure. ( MELSEC iQ-R CPU Module User's Manual (Startup))
Action
Check and correct the IP address of the external device.
• If the connection with the external device is not opened, perform the open
*1*2
processing.
• If an error occurs, check and eliminate the error cause.
• If the send/receive processing has not been executed, check and correct
the execution condition of the send/receive processing.
• If send/receive processing has completed with an error, check the error
code in the completion status and eliminate the error cause.
Correct the predefined protocol settings and program If inappropriate protocol
is used.
For appropriate protocol for the external device, refer to the manual for the
device used.
Correct the communication method setting if an item other than "Predefined
Protocol" is set. ( Page 244 External Device Configuration)
*1
If 'Predefined protocol ready' (Un\G1901002.0) is off, write the protocol setting
data to the module.
*3
3 TROUBLESHOOTING
3.4 Troubleshooting by Symptom
3
299