■Cause of error at abnormal completion
If the IP address storage area is not cleared correctly, the cause of the error is stored as follows:
Module
Storage location
CPU module (built-in
'IP address storage area
Ethernet port part)
clear error cause' (SD1527)
RJ71EN71, RnENCPU
'IP address storage area
(network part)
clear error cause'
(Un\G11714)

Checking the IP address

Checking with the buffer memory
Check with the following buffer memory areas.
Item
Own node IP address
Subnet mask
Default gateway IP address
Own node network number
Station number
Transient transmission group number
Checking with module diagnostics
Check by using the [Module Information List] tab of the "Module Diagnostics" window. ( Page 283 Module Information
List)

Checking the operating status

For the RJ71EN71 or the RnENCPU (network part), when operation is performed based on the IP address of the IP address
storage area, 'IP address change function operating status' (Un\G11715.0) turns on.

Precautions

The following section lists the precautions for using the IP address.
Power off and reset operation
Do not power off or reset when writing to or clearing the IP address storage area. The values may not be applied onto the IP
address storage area. Power off or reset after checking the falling edge of the IP address storage area write request or IP
address storage area clear request.
Parameter IP address
For the IP address of the Ethernet-equipped module, the value in the IP address storage area has precedence over the
parameter value. When using the IP address specified with the parameters, clear the IP address storage area.
Stored value
Cause of error
200H
Error occurred during clearing.
400H
Clearing was started during the write processing.
200H
Error occurred during clearing.
400H
Clearing was started during the write processing.
CPU module (built-in Ethernet port part)
Un\G50 to Un\G51
Un\G60 to Un\G61
Un\G64 to Un\G65
Un\G77
Un\G78
RJ71EN71, RnENCPU (network part)
Un\G4 to Un\G5
Un\G14 to Un\G15
Un\G18 to Un\G19
Un\G31
Un\G32
Un\G33
1 FUNCTIONS
1.16 IP Address Change Function
1
217