Mitsubishi Electric MELSEC iQ-R Series User Manual page 80

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

CH1 Warning output flag
The statuses of the upper limit and lower limit warnings can be checked.
b15 b14 b13 b12 b11 b10 b9
0
0
0
0
0
(1) Lower limit warning (0: Normal, 1: Range exceeded)
(2) Upper limit warning (0: Normal, 1: Range exceeded)
■Buffer memory addresses
The following shows the buffer memory addresses of this area.
Buffer memory name
CH Warning output flag
CH Warning output flag (when Q series-compatible
mode is used)
■Warning output flag status
When the sampling pulse number meets one of the following conditions, Range exceeded (1) is stored in the appropriate bit of
'CH1 Warning output flag' (Un\G8).
• The value is greater than or equal to the setting value of 'CH1 Warning output setting value upper/upper limit' (Un\G137).
• The value is less than or equal to the setting value of 'CH1 Warning output setting value lower/lower limit' (Un\G140).
■Clearing the warning output flag
• If an upper limit warning has occurred, Normal (0) is stored in bit 8 of 'CH1 Warning output flag' (Un\G8) when the sampling
pulse number becomes less than the setting value of 'CH1 Warning output setting value upper/lower limit' (Un\G138).
• If a lower limit warning has occurred, Normal (0) is stored in bit 0 of 'CH1 Warning output flag' (Un\G8) when the sampling
pulse number becomes greater than the setting value of 'CH1 Warning output setting value lower/upper limit' (Un\G139).
CH1 Error code
The latest error code detected in the pulse input module is stored. For details, refer to the following.
Page 52 List of Error Codes
■Buffer memory addresses
The following shows the buffer memory addresses of this area.
Buffer memory name
CH Error code
CH Error code (when Q series-compatible mode is
used)
■Clearing an error
Turn on and off 'CH1 Error reset request' (Y8).
CH1 Alarm code
The latest alarm code detected in the pulse input module is stored. For details, refer to the following.
Page 54 List of Alarm Codes
■Buffer memory addresses
The following shows the buffer memory addresses of this area.
Buffer memory name
CH Alarm code
CH Alarm code (when Q series-compatible mode is
used)
■Clearing an alarm
Turn on and off 'CH1 Error reset request' (Y8).
APPX
78
Appendix 3 Buffer Memory Areas
b8
b7
b6
b5
b4
0
0
0
0
0
0
(2)
CH1
8
18
CH1
9
16
CH1
10
25
b3
b2
b1
b0
0
0
0
(1)
CH2
CH3
CH4
24
40
56
50
82
114
CH2
CH3
CH4
25
41
57
48
80
112
CH2
CH3
CH4
26
42
58
57
89
121
CH5
CH6
CH7
72
88
104
146
178
210
CH5
CH6
CH7
73
89
105
144
176
208
CH5
CH6
CH7
74
90
106
153
185
217
CH8
120
242
CH8
121
240
CH8
122
249

Advertisement