Precautions
• When 'Condition target setting [n]' (Un\G728 to Un\G743) is Invalid (0), an interrupt request is not sent to the CPU module.
• If an interrupt factor occurs when 'Interrupt factor mask [n]' (Un\G632 to Un\G647) is Mask (Interrupt unused) (0), an
interrupt request is not sent to the CPU module. However, 'Interrupt factor detection flag [n]' (Un\G600 to Un\G615) is
changed to Interrupt factor (1).
• To reset the interrupt factor, specify Reset request (1) until 'Interrupt factor detection flag [n]' (Un\G600 to Un\G615)
changes to No interrupt factor (0).
• Resetting interrupt factors is executed only when 'Interrupt factor reset request [n]' (Un\G664 to Un\G679) changes from No
reset request (0) to Reset request (1).
• Multiple interrupt pointers can share the same setting of 'Condition target setting [n]' (Un\G728 to Un\G743). When multiple
interrupt pointers have shared the same setting of 'Condition target setting [n]' (Un\G728 to Un\G743) and interrupts occur,
interrupt programs are executed in order of priority of the interrupt pointers. For the priority of the interrupt pointers, refer to
the following.
MELSEC iQ-R CPU Module User's Manual (Application)
• When multiple interrupt factors occur at the same time, the CPU module executes multiple interrupt programs at the same
time. When it will take a long time for all interrupt programs to finish executing, the CPU module judges that the programs
cannot be normally completed with the scan monitoring function, and a CPU error may occur. When a CPU error occurs,
refer to the following.
MELSEC iQ-R CPU Module User's Manual (Application)
1 FUNCTIONS
34
1.9 Interrupt Function