Panasonic EBL512 Operating Instructions Manual page 96

Fire alarm system ebl512
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01457
"A"
The zone(s) will stay in test mode until the test mode is ended but after 60 minutes or if you press
"Return" two times, you will be logged out from menu H1.
Perform the test as quickly as possible, since the output(s) for routing equipment (fire brigade tx) are disabled
(also the parts of the zones in test mode, not visible for the test personnel, are disabled).
In order to shorten the testing time, any time delay for the detectors / zones in test mode will be "disabled",
i.e. fire alarm will be detected faster than normally.
In the tested alarm point, the LED will light up, and the LEDs "Fire" (L1) in the c.i.e. will light up, about ten
seconds, then the alarm point will be automatically reset. The printer, if available, will print out every tested
alarm point (Zone: xxx Address: xx Time: HH.MM).
A sensor in test mode will not be able to activate fault.
After 60 minutes or
"Return"
"Return"
(When required:
"Access", "code")
"A"
"A"
Some national regulations also require a routine test of the routing equipment. Press "A" for no test and press
"1" and "A" to start such a test. The following will happen (in the system):
 The c.i.e. "Fault tx" output will be de-activated
A 60 seconds count-down starts.
 After 30 seconds, also the c.i.e. "Fire brigade tx" output (and corresponding programmable outputs
type 4 = routing equipment) will be activated, indicated by the LED "Fire brigade tx" (L15).
 After another 30 seconds, the test will be ended and the outputs and LEDs will return to "normal".
"1", "A"
"A"
Rev: -
Operating Instructions Fire alarm system EBL512, V2.7.x
Zones are set in test mode
wait....
Zone in TEST MODE:
001 002 003 004
Zones in test mode: 001, 002, 003, 004
NOTE! See chapter "Alphanumeric display (LCD) in
EBL512", page 21 regarding priority order.
Zone in TEST MODE:
001 002 003 004
Test of routing equipment? 0
(1 = Yes, 0 = No)
Test of routing equipment in progress.
nn seconds left.
Monthly test is completed!
Perform monthly test
93
This output is activated in normal state.
End test:
ACCEPT
End test:
ACCEPT
ACCEPT
93
, indicated by the LED "Fault tx activated" (L11).
ACCEPT
ACCEPT? H1
94
LED "Test mode" (L9)
will light up.
Perform the tests.
You are no longer in menu
H1 but still in test mode.
Press "A" to end the test
mode.
The LED "Test mode" is
turned OFF.
"nn" starts at 60 and will
count down to 00.
Scroll or press "Return" to
log off.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents