Alert Annunciation (Aa Alarm) - Panasonic EBL512 Operating Instructions Manual

Fire alarm system ebl512
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01457
Rev: -
15.2.2.6
15.2.2.7
15.2.3
Operating Instructions Fire alarm system EBL512, V2.7.x
ZONE: 123
Re-enable zone: ZZZ
This is a list of disabled zones. Scroll to or write the wanted zone
number and press "A". If more zones are to be re-enabled, repeat the
procedure.
Disable / Re-enable control (X6)
ZONE: 123
Disable/Re-enable control
Press "A". E.g.:
ZONE: 123
Dis(=0) or re-en(=1) control? 1
To disable, press "0" and "A". (To re-enable, press "1" and "A".). For
more information, see chapter "Disable / Re-enable all control, exting.
and ventilation outputs (H2/B8), page 106.
Disable / Re-enable alarm devices (X7)
ZONE: 123
Disable/Re-enable alarm dev. ACCEPT?
Press "A". E.g.:
ZONE: 123
Dis(=0) or re-en(=1) alarm dev?1 ACCEPT?
To disable, press "0" and "A". (To re-enable, press "1" and "A".). For
more information, see chapter "Disable / Re-enable alarm devices
(H2/B9), page 107.

Alert Annunciation (AA alarm)

When the AA function is enabled, indicated by the LED "Fire brigade
tx delay" (L16), the indications, print-outs, actions etc. are as for a
normal fire alarm except the c.i.e. output for routing equipment
(fire brigade tx) will not be activated. The AA alarm has to be
acknowledged within an acknowledge time and reset within an
investigation time, otherwise the output(s) for routing equipment (fire
brigade tx) will be activated. See EBL512 Planning Instructions for
more information regarding the AA function. Acknowledgement
and reset of the AA alarm can be done on a Display unit 2235
AA unit 1735 / 1736 or an AA controller 1740. See also chapter
"Alarm reset", page 51.
52
In the "Polish" (CNBOP) and "Czech" conventions, the push button
"Evacuate" (P5) can be used for "AA Acknowledge".
53
LED "Acknowledge" on 2235 is indicating that the push button
"Acknowledge" has been activated. A busy system can cause a time delay
(up to 10 seconds) before the fire alarm is acknowledged.
46
LAST: 789
No.: 003
ACCEPT?
LAST: 789
No.: 003
ACCEPT?
LAST: 789
No.: 003
ACCEPT?
LAST: 789
No.: 003
LAST: 789
No.: 003
X6
X7
52
53
, an