Operating Instructions Fire alarm system EBL512, V2.7.x
New system program (S/W) version
download
The latest software (S/W) version of the EBL512 system program is
factory downloaded before the delivery.
development and improvement, different S/W versions can be found.
The valid S/W version can be read in menu H3 or via Win512. New
S/W can on site be downloaded via Win512.
New S/W for the 1728, 1735 / 1736 & 1826 / 1828 units (connected to
an Ext. FBP/DU interface board 1587) can also on site be downloaded
via Win512. See the "Technical Description" for the unit respectively.

A single control unit (c.i.e.)

A single c.i.e. must not have a TLON connection board 1590
82
mounted.
To download a new software (system program) version, a PC and
Win512 are used. Before download, the PC has to be connected to
the "D" connector J1 in the control unit main board 1556 in question.
1. Start Win512.
In the "Tools" menu open the "Download
software" dialog box and do the required settings, e.g. the path for
the S/W (*.BIN) file and/or the language (*.SST) file
forget to mark the checkbox respectively.
2. Set the c.i.e. in "Bootstrap mode", i.e. set jumper "JP1 (BOOT)" in
position on the main board 1556.
3. Do a reset/restart, i.e. set jumper "JP4 (RESET)" in position
momentarily (approx. 1 second).
4. The buzzer will now sound intermittent and LED "LD101" starts
84
blinking
, indicating that the control unit is in "Bootstrap mode".
5. Start the downloading (click "Download"). The buzzer will now
be silenced and LED "LD101" is turned on (continuously).
6. During the download of the S/W and/or text file, some
information will be shown in the Win512 log view and when the
download is ready, "Downloading completed successfully." will
81
It is recommended that the two first digits in the EBL512 S/W version and
the Win512 version are the same, e.g. for EBL version 2.7.x shall Win512
version 2.7.x be used.
82
When a c.i.e. has a TLON connection board 1590 mounted, it is expected
to be one c.i.e. in a TLON network and TLON network programming is
required.
83
If the new S/W file comes together with a text file, download it as well.
84
Also the LED "System fault" (L14) starts blinking.