Perform Zone Test (Test Mode) (H7) - Panasonic EBL512 Operating Instructions Manual

Fire alarm system ebl512
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01457
30
Action
"Access"
Scroll to menu H7.
"A"
Write zone numbers
(e.g. 001, 002, 003,
004).
"A"
The zone(s) will stay in test mode until the test mode is ended but after 60 minutes or if you press
"Return" two times you will be logged out from menu H7.
Perform the test as quickly as possible, since the output(s) for routing equipment (fire brigade tx) are disabled
(also the parts of the zones in test mode, not visible for the test personnel, are disabled).
In order to shorten the testing time, any time delay for the detectors / zones in test mode will be "disabled",
i.e. fire alarm will be detected faster than normally.
In the tested alarm point, the LED will light up, and the LEDs "Fire" (L1) in the C.U. will light up, about ten
seconds, then the alarm point will be automatically reset. The printer, if available, will print out every tested
alarm point (Zone: xxx Address: xx Time: HH.MM).
A sensor in test mode will not be able to activate fault.
Rev: -
Operating Instructions Fire alarm system EBL512, V2.7.x
Perform ZONE TEST (test mode)
(H7)
Normally, zones are tested during the monthly test via menu H1. Via
this menu (H7) it is possible to perform the zone test solely.
In test mode, only the alarm points are tested, i.e. no outputs (no
sounders) will be activated during the test. (Alarm devices can be
tested via menu H8/S7.)
If a real fire alarm is activated, for example by an alarm point not in
test mode, the normal fire alarm functions will be activated, i.e. fire
alarm presentation, outputs (sounders) activated, routing equipment
(fire brigade tx) activated, etc.
See also chapter "Alphanumeric display (LCD) in EBL512", page 21.
NOTE! If the control unit door is left open, the output(s) for routing
equipment (fire brigade tx) might be disabled (if set so in Win512).
There will be an automatic ending of the test mode one hour after the
latest tested alarm point.
Text in display
Perform ZONE TEST
Zone to be set in TEST MODE:
??? ??? ??? ???
Zone to be set in TEST MODE:
001 002 003 004
Zones are set in test mode
wait....
Zone in TEST MODE:
001 002 003 004
ACCEPT? H7
Start test:
ACCEPT
Start test:
ACCEPT
End test:
ACCEPT
139
Comments
According to chapter
"Access", see page 92.
Press "A" to start the test
mode.
LED "Test mode" (L9)
will light up.
Perform the tests.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents