Safe Shut Down Of Control Unit (H8/S8) - Panasonic EBL512 Operating Instructions Manual

Fire alarm system ebl512
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01457
31.9
Action
"Access"
Scroll to menu S8.
"A"
Write the C.U. number,
"1" (=yes) and
"A"
Rev: -
Operating Instructions Fire alarm system EBL512, V2.7.x

Safe shut down of control unit (H8/S8)

It's not recommended to power off a control unit (i.e. no 230 V AC
and no battery) without first doing a safe shut down of control unit.
Safe shut down will save the SSW and put the CPU at rest. See also
chapter "Restart", page 88.
It's recommended to do a safe shut down after commissioning the
installation and after the calibration of supervised outputs, change of
access code etc. in order to save the new values, codes etc.
Safe shut down can be performed from any control unit and any
control unit can be selected, e.g. a control unit without a front has to
be shut down from another control unit.
NOTE! By restart and power off, the Fault tx output(s) will be
"activated".
Text in display
Safe shut down of control unit
Shut down control unit 00 ? 0
(1 = Yes, 0 = No)
Please Wait ...
In the CU that will be shut down (when a front is available):
Ready for shut-down, break the power.
Automatic restart within nnn seconds!
In the CU:s that will not be shut down:
Control unit xx ready for power off
No reply from the selected CU xx, i.e. no safe shut down:
No reply from control unit.
FAULT: Restart CU xx code xx
Date: mm-dd
Time: hh:mm
NOTE! The date is in the Ukrainian convention (S/W
version > 2.2.3) and the Australian convention shown
as DD-MM.
118
If not, a fault ("FAULT: Read/write site data (SSW), CU xx") might be
generated when you power up the control unit again.
ACCEPT?
ACCEPT?
yyyyyyy
Serviced
149
118
Comments
According to chapter
"Access code for
maintenance", see page
141.
S8
Shown for 3 sec. then one
of the three alternatives:
Count down starts from
nnn = 300 seconds.
Disconnect the power
supply (mains and battery).
When the power supply is
connected again or after
300 seconds (if powered
all time), there will be an
automatic reset / restart.
After restart / power on
(see page 88), there will be
a fault activated. This fault
has to be acknowledged,
see chapter "Acknowledge
FAULTS (H6)", page 138.