PAC8000 PROFINET Scanner Specifications

1.3
PROFINET Support
RX3i PLC CPU Version
Required
Proficy Machine Edition
Version Required
Power Requirements
Module Dimensions
Carrier Required
Operating Temperature
Range
Number of Port
Connectors
USB Connector (for
firmware upgrades)
PNS Status and Control
Bits
I/O Data Update on the
PROFINET LAN
Number of IP addresses
Number of MAC
Addresses
I/O Station Maximum
Limits
RoHS Compliance
Configuration
For product standards, general operating specifications, and installation requirements, refer
to the PAC8000 IO modules Manual, INM8200.pdf.
GFK-2839B
PROFINET Version 2.3 Class A IO-Device
Redundantly controlled operation conforms to PROFINET V2.3 Type
S2 System Redundancy.
Firmware version 7.0 or later
Version 7.5 SIM 3 or later
V2.3 GSDML and Proficy Machine Edition/3rd-Party tools.
8515-BI-PN 4.5 Watts (5.5 Watts Max)
8516-BI-PN 6.0 Watts (7.2 Watts Max)
Length: 160.3mm (6.31"), Width: 128.3mm (5.05")
Thickness 47.78mm (1.88")
8752-CA-NS : PAC8000 Node Service Carrier
8515-BI-PN -40˚C to +70˚C
8516-BI-PN -40˚C to +70˚C
Horizontal DIN rail mounting.
Optimum orientation is when the carrier is mounted in a vertical plane
with field terminals for communication cables located below the
modules.
8515-BI-PN : Two RJ-45
8516-BI-PN : Two SC-Duplex
One Micro-B connector. USB 2.0 compliant running at full speed
(12 MHz)
64 input status bits and 48 output control bits
Configurable: 1ms, 2ms, 4ms, 8ms, 16ms, 32ms, 64ms, 128ms, 256ms
and 512ms (Recommended is 4 ms and above)
One. Supports Classless Inter-Domain Routing (CIDR)
Three. One per external port and one internal. External MAC addresses
are only used for specialized Ethernet protocols such as MRP or LLDP
Number of IO Modules per
Node
IO data per station
Yes
Configured using Proficy Machine Edition when used with a
PACSystems RX3i PROFINET Controller (PNC) module, as part of an
RX3i PROFINET network.
V2.3 GSDML file is available for import into 3
PAC8000* IO PROFINET Scanner User's Manual–September 2017
32
2880 bytes total
1440 bytes of input data
1440 bytes of output data