8 - Default parameters

Ekip Dip default parameters The Ekip Dip trip units are supplied with the following default parameters, some adjustable with the front DIPs
52 | © 2017 ABB | 1SDH000999R0002 - ECN000058721 - Rev. B
(protections, Frequency, Neutral), other via front bus.
Protection/Parameter
L
S
(1)
I
G
(1)
Frequency
Neutral
Hardware Trip
Monitor time
Local Bus
Alive LED
Maintenance
(1)
S Protection available with LSI and LSIG versions of the trip unit. G Protection available with LSIG version.
Value
1 In; 144 s
Off; 0.1 s
4 In
Off; 0.1 s
50 Hz (IEC) / 60 Hz (UL)
Off (for three-pole circuit breakers).
50 % (for four-pole circuit-breaker)
Disabled
5 minutes
Disabled
Disabled (Power-on LED fixed)
Off