B.4 MEMORY MAPPING
bitmask
Input Point Block
12
Contact Inputs 81 to 96
13
Contact Outputs 1 to 16
14
Contact Outputs 17 to 32
15
Contact Outputs 33 to 48
16
Contact Outputs 49 to 64
17
Remote Inputs 1 to 16
B
18
Remote Inputs 17 to 32
19
Remote Devs 1 to 16
20
Elements 1 to 16
21
Elements 17 to 32
22
Elements 33 to 48
23
Elements 49 to 64
24
Elements 65 to 80
25
Elements 81 to 96
26
Elements 97 to 112
27
Elements 113 to 128
28
Elements 129 to 144
29
Elements 145 to 160
30
Elements 161 to 176
31
Elements 177 to 192
32
Elements 193 to 208
33
Elements 209 to 224
34
Elements 225 to 240
35
Elements 241 to 256
36
Elements 257 to 272
37
Elements 273 to 288
38
Elements 289 to 304
39
Elements 305 to 320
40
Elements 321 to 336
41
Elements 337 to 352
42
Elements 353 to 368
43
Elements 369 to 384
44
Elements 385 to 400
45
Elements 401 to 406
46
Elements 417 to 432
47
Elements 433 to 448
48
Elements 449 to 464
49
Elements 465 to 480
50
Elements 481 to 496
51
Elements 497 to 512
52
Elements 513 to 528
53
Elements 529 to 544
54
Elements 545 to 560
55
LED States 1 to 16
56
LED States 17 to 32
57
Self Tests 1 to 16
58
Self Tests 17 to 32
F200
TEXT40: 40-CHARACTER ASCII TEXT
20 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB
B-50
F201
TEXT8: 8-CHARACTER ASCII PASSCODE
4 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB
F202
TEXT20: 20-CHARACTER ASCII TEXT
10 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB
F203
TEXT16: 16-CHARACTER ASCII TEXT
F204
TEXT80: 80-CHARACTER ASCII TEXT
F205
TEXT12: 12-CHARACTER ASCII TEXT
F206
TEXT6: 6-CHARACTER ASCII TEXT
F207
TEXT4: 4-CHARACTER ASCII TEXT
F208
TEXT2: 2-CHARACTER ASCII TEXT
F222
ENUMERATION: TEST ENUMERATION
0 = Test Enumeration 0, 1 = Test Enumeration 1
F240
ENUMERATION: V/HZ CURVES
0 = Definite Time, 1 = Inverse A, 2 = Inverse B, 3 = Inverse C, 4 =
FlexCurve™ A, 5 = FlexCurve™ B, 6 = FlexCurve™ C, 7 = Flex-
Curve™ D
F300
UR_UINT16: FLEXLOGIC™ BASE TYPE (6-bit type)
The FlexLogic™ BASE type is 6 bits and is combined with a 9 bit
descriptor and 1 bit for protection element to form a 16 bit value.
The combined bits are of the form: PTTTTTTDDDDDDDDD,
where P bit if set, indicates that the FlexLogic™ type is associated
with a protection element state and T represents bits for the BASE
type, and D represents bits for the descriptor.
The values in square brackets indicate the base type with P prefix
[PTTTTTT] and the values in round brackets indicate the descrip-
tor range.
[0] Off(0) this is boolean FALSE value
[0] On (1)This is boolean TRUE value
[2] CONTACT INPUTS (1 - 96)
T60 Transformer Management Relay
APPENDIX B
GE Multilin

Advertisement