GE t60 Instruction Manual page 186

Ur series transformer management relay
Hide thumbs Also See for t60:
Table of Contents

Advertisement

5.5 GROUPED ELEMENTS
d) NEUTRAL OVERVOLTAGE (ANSI 59N)
PATH: SETTINGS
GROUPED ELEMENTS
NEUTRAL OV1
The Neutral Overvoltage element can be used to detect asymmetrical system voltage condition due to a ground fault or to
5
the loss of one or two phases of the source. The element responds to the system neutral voltage (3V_0), calculated from
the phase voltages. The nominal secondary voltage of the phase voltage channels entered under
SETUP
AC INPUTS
VT errors and normal voltage unbalance must be considered when setting this element. This function requires the VTs to
be Wye connected.
SETTING
NEUTRAL OV1
FUNCTION:
Disabled=0
Enabled=1
SETTING
NEUTRAL OV1 BLOCK:
Off=0
SETTING
NEUTRAL OV1 SIGNAL
SOURCE:
ZERO SEQ VOLT (V_0)
5-108
SETTING GROUP 1(6)
NEUTRAL OV1
FUNCTION: Disabled
NEUTRAL OV1 SIGNAL
MESSAGE
SOURCE: SRC 1
NEUTRAL OV1 PICKUP:
MESSAGE
0.300 pu
NEUTRAL OV1 PICKUP:
MESSAGE
DELAY: 1.00 s
NEUTRAL OV1 RESET:
MESSAGE
DELAY: 1.00 s
NEUTRAL OV1 BLOCK:
MESSAGE
Off
NEUTRAL OV1 TARGET:
MESSAGE
Self-reset
NEUTRAL OV1 EVENTS:
MESSAGE
Disabled
VOLTAGE BANK
PHASE VT SECONDARY
SETTING
NEUTRAL OV1 PICKUP:
RUN
AND
<
3V_0 Pickup
Figure 5–61: NEUTRAL OVERVOLTAGE1 SCHEME LOGIC
T60 Transformer Management Relay
VOLTAGE ELEMENTS
NEUTRAL OV1
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 0.000 to 1.250 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
is the p.u. base used when setting the pickup level.
SETTING
NEUTRAL OV1 PICKUP
DELAY :
NEUTRAL OV1 RESET
DELAY :
t
PKP
t
RST
5 SETTINGS
SETTINGS
SYSTEM
FLEXLOGIC OPERANDS
NEUTRAL OV1 OP
NEUTRAL OV1 DPO
NEUTRAL OV1 PKP
827848A1.CDR