[DESIGN PRECAUTIONS]
The display section of the GT1595-X is an analog-resistive type touch panel.
If you touch the display section simultaneously in 2 points or more, the switch
that is located around the center of the touched point, if any, may operate.
Do not touch the display section in 2 points or more simultaneously.
Doing so may cause an accident due to incorrect output or malfunction.
Do not bundle the control and communication cables with main-circuit, power
or other wiring.
Run the above cables separately from such wiring and keep them a minimum
of 100mm apart.
Not doing so noise can cause a malfunction.
Do not press the GOT display section with a pointed material as a pen or
driver.
Doing so can result in a damage or failure of the display section.
[MOUNTING PRECAUTIONS]
Be sure to shut off all phases of the external power supply used by the system
before mounting or removing the GOT main unit to/from the panel.
Not doing so can cause the unit to fail or malfunction.
Be sure to shut off all phases of the external power supply used by the system
before mounting or removing the communication unit, option function board or
multi-color display board onto/from the GOT.
Not doing so can cause the unit to fail or malfunction.
When installing the multi-color display board, wear an earth band etc. to avoid
the static electricity.
Not doing so can cause a unit corruption.
DANGER
CAUTION
DANGER
A-3