POINT
1. Separate the grounding of the lightning surge absorber (E1) from
the grounding of the GOT (E2).
2. Select an appropriate lightning surge absorber so that the supply
voltage does not exceed the maximum allowable circuit voltage
of the surge absorber even when it rises to the maximum.

6.3 Wiring to GOT Power Section

This section provides an example for connecting power cables and
ground cables to the power terminals situated on the back of the GOT.
AC
Fuse
AD
DC
24V DC
Ground cables
100/110V AC
Grounding
In the case of 100V AC
GOT
INPUT
100-240VAC
(LG) (FG)
In the case of 24V DC (GT1595,
GOT
INPUT
24VDC
-
+
(LG) (FG)
In the case of 24V DC (GT155
GOT
INPUT
24VDC
-
+
(FG)