Protection And Other Logical Nodes - GE T60 Instruction Manual

Ur series
Hide thumbs Also See for T60:
Table of Contents

Advertisement

APPENDIX C
MMXU data is provided in two forms: instantaneous and deadband. The instantaneous values are updated every time a
read operation is performed by a client. The deadband values are calculated as described in IEC 61850 parts 7-1 and 7-3.
The selection of appropriate deadband settings for the T60 is described in chapter 5 of this manual.
IEC 61850 buffered and unbuffered reporting capability is available in all MMXU logical nodes. MMXUx logical nodes pro-
vide the following data for each source:
MMXU1.ST.TotW: three-phase real power
MMXU1.ST.TotVAr: three-phase reactive power
MMXU1.ST.TotVA: three-phase apparent power
MMXU1.ST.TotPF: three-phase power factor
MMXU1.ST.Hz: frequency
MMXU1.ST.PPV.phsAB: phase AB voltage magnitude and angle
MMXU1.ST.PPV.phsBC: phase BC voltage magnitude and angle
MMXU1.ST.PPV.phsCA: Phase CA voltage magnitude and angle
MMXU1.ST.PhV.phsA: phase AG voltage magnitude and angle
MMXU1.ST.PhV.phsB: phase BG voltage magnitude and angle
MMXU1.ST.PhV.phsC: phase CG voltage magnitude and angle
MMXU1.ST.A.phsA: phase A current magnitude and angle
MMXU1.ST.A.phsB: phase B current magnitude and angle
MMXU1.ST.A.phsC: phase C current magnitude and angle
MMXU1.ST.A.neut: ground current magnitude and angle
MMXU1.ST.W.phsA: phase A real power
MMXU1.ST.W.phsB: phase B real power
MMXU1.ST.W.phsC: phase C real power
MMXU1.ST.VAr.phsA: phase A reactive power
MMXU1.ST.VAr.phsB: phase B reactive power
MMXU1.ST.VAr.phsC: phase C reactive power
MMXU1.ST.VA.phsA: phase A apparent power
MMXU1.ST.VA.phsB: phase B apparent power
MMXU1.ST.VA.phsC: phase C apparent power
MMXU1.ST.PF.phsA: phase A power factor
MMXU1.ST.PF.phsB: phase B power factor
MMXU1.ST.PF.phsC: phase C power factor
The following list describes the protection elements for all UR-series relays. The T60 relay will contain a subset of protec-
tion elements from this list.
PDIF: transformer instantaneous differential, transformer percent differential
PDIS: phase distance, ground distance
PIOC: phase instantaneous overcurrent, neutral instantaneous overcurrent, ground instantaneous overcurrent, nega-
tive-sequence instantaneous overcurrent.
PTOC: phase time overcurrent, neutral time overcurrent, ground time overcurrent, negative-sequence time overcur-
rent, neutral directional overcurrent, negative-sequence directional overcurrent
GE Multilin
Courtesy of NationalSwitchgear.com
C.2.6 PROTECTION AND OTHER LOGICAL NODES
T60 Transformer Management Relay
C.2 SERVER DATA ORGANIZATION
C
C-3