5.4 FLEXLOGIC™
The operands available for this relay are listed alphabetically by types in the following table.
Table 5–8: T60 FLEXLOGIC™ OPERANDS (Sheet 1 of 5)
OPERAND TYPE
CONTROL
PUSHBUTTONS
5
DIRECT DEVICES
DIRECT INPUT/
OUTPUT
CHANNEL
MONITORING
ELEMENT:
Auxiliary
overvoltage
ELEMENT:
Auxiliary
undervoltage
ELEMENT:
Breaker arcing
ELEMENT:
Digital counters
ELEMENT:
Digital elements
ELEMENT:
FlexElements™
ELEMENT:
Ground
instantaneous
overcurrent
ELEMENT:
Ground time
overcurrent
ELEMENT
Non-volatile latches
ELEMENT:
Neutral
instantaneous
overcurrent
ELEMENT:
Neutral overvoltage
5-80
Courtesy of NationalSwitchgear.com
OPERAND SYNTAX
CONTROL PUSHBTN 1 ON
CONTROL PUSHBTN 2 ON
CONTROL PUSHBTN 3 ON
CONTROL PUSHBTN 4 ON
CONTROL PUSHBTN 5 ON
CONTROL PUSHBTN 6 ON
CONTROL PUSHBTN 7 ON
DIRECT DEVICE 1On
DIRECT DEVICE 16On
DIRECT DEVICE 1Off
DIRECT DEVICE 16Off
DIR IO CH1(2) CRC ALARM
DIR IO CRC ALARM
DIR IO CH1(2) UNRET ALM
DIR IO UNRET ALM
AUX OV1 PKP
AUX OV1 DPO
AUX OV1 OP
AUX OV2 to AUX OV3
AUX UV1 PKP
AUX UV1 DPO
AUX UV1 OP
AUX UV2 to AUX UV3
BKR ARC 1 OP
BKR ARC 2 OP
Counter 1 HI
Counter 1 EQL
Counter 1 LO
Counter 2 to Counter 8
Dig Element 1 PKP
Dig Element 1 OP
Dig Element 1 DPO
Dig Element 2 to Dig Element 48
FxE 1 PKP
FxE 1 OP
FxE 1 DPO
FxE 2 to FxE 16
GROUND IOC1 PKP
GROUND IOC1 OP
GROUND IOC1 DPO
GROUND IOC2 to IOC8
GROUND TOC1 PKP
GROUND TOC1 OP
GROUND TOC1 DPO
GROUND TOC2 to TOC6
LATCH 1 ON
LATCH 1 OFF
LATCH 2 to LATCH 16
NEUTRAL IOC1 PKP
NEUTRAL IOC1 OP
NEUTRAL IOC1 DPO
NEUTRAL IOC2 to IOC8
NEUTRAL OV1 PKP
NEUTRAL OV1 DPO
NEUTRAL OV1 OP
T60 Transformer Management Relay
OPERAND DESCRIPTION
Control pushbutton 1 is being pressed
Control pushbutton 2 is being pressed
Control pushbutton 3 is being pressed
Control pushbutton 4 is being pressed
Control pushbutton 5 is being pressed
Control pushbutton 6 is being pressed
Control pushbutton 7 is being pressed
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
The rate of direct input messages received on channel 1(2) and failing the
CRC exceeded the user-specified level.
The rate of direct input messages failing the CRC exceeded the user-
specified level on channel 1 or 2.
The rate of returned direct input/output messages on channel 1(2) exceeded
the user-specified level (ring configurations only).
The rate of returned direct input/output messages exceeded the user-
specified level on channel 1 or 2 (ring configurations only).
Auxiliary overvoltage element has picked up
Auxiliary overvoltage element has dropped out
Auxiliary overvoltage element has operated
Same set of operands as shown for AUX OV1
Auxiliary undervoltage element has picked up
Auxiliary undervoltage element has dropped out
Auxiliary undervoltage element has operated
Same set of operands as shown for AUX UV1
Breaker arcing current 1 has operated
Breaker arcing current 2 has operated
Digital counter 1 output is 'more than' comparison value
Digital counter 1 output is 'equal to' comparison value
Digital counter 1 output is 'less than' comparison value
Same set of operands as shown for Counter 1
Digital Element 1 is picked up
Digital Element 1 is operated
Digital Element 1 is dropped out
Same set of operands as shown for Dig Element 1
FlexElement™ 1 has picked up
FlexElement™ 1 has operated
FlexElement™ 1 has dropped out
Same set of operands as shown for FxE 1
Ground instantaneous overcurrent 1 has picked up
Ground instantaneous overcurrent 1 has operated
Ground instantaneous overcurrent 1 has dropped out
Same set of operands as shown for GROUND IOC 1
Ground time overcurrent 1 has picked up
Ground time overcurrent 1 has operated
Ground time overcurrent 1 has dropped out
Same set of operands as shown for GROUND TOC1
Non-volatile latch 1 is ON (Logic = 1)
Non-voltage latch 1 is OFF (Logic = 0)
Same set of operands as shown for LATCH 1
Neutral instantaneous overcurrent 1 has picked up
Neutral instantaneous overcurrent 1 has operated
Neutral instantaneous overcurrent 1 has dropped out
Same set of operands as shown for NEUTRAL IOC1
Neutral overvoltage element 1 has picked up
Neutral overvoltage element 1 has dropped out
Neutral overvoltage element 1 has operated
5 SETTINGS