B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 21 of 46)
ADDR
REGISTER NAME
7005
Phase Undervoltage 1 Minimum Voltage
7006
Phase Undervoltage 1 Block
7007
Phase Undervoltage 1 Target
7008
Phase Undervoltage 1 Events
7009
Phase Undervoltage 1 Measurement Mode
B
700A
Reserved (6 items)
7013
...Repeated for Phase Undervoltage 2
Phase Overvoltage (Read/Write Grouped Setting)
7040
Phase Overvoltage 1 Function
7041
Phase Overvoltage 1 Source
7042
Phase Overvoltage 1 Pickup
7043
Phase Overvoltage 1 Delay
7044
Phase Overvoltage 1 Reset Delay
7045
Phase Overvoltage 1 Block
7046
Phase Overvoltage 1 Target
7047
Phase Overvoltage 1 Events
7048
Reserved (8 items)
Phase Directional Overcurrent (Read/Write Grouped Setting) (2 modules)
7260
Phase Directional Overcurrent 1 Function
7261
Phase Directional Overcurrent 1 Source
7262
Phase Directional Overcurrent 1 Block
7263
Phase Directional Overcurrent 1 ECA
7264
Phase Directional Overcurrent 1 Pol V Threshold
7265
Phase Directional Overcurrent 1 Block Overcurrent
7266
Phase Directional Overcurrent 1 Target
7267
Phase Directional Overcurrent 1 Events
7268
Reserved (8 items)
7270
...Repeated for Phase Directional Overcurrent 2
Neutral Directional Overcurrent (Read/Write Grouped Setting) (2 modules)
7280
Neutral Directional Overcurrent 1 Function
7281
Neutral Directional Overcurrent 1 Source
7282
Neutral Directional Overcurrent 1 Polarizing
7283
Neutral Directional Overcurrent 1 Forward ECA
7284
Neutral Directional Overcurrent 1 Forward Limit Angle
7285
Neutral Directional Overcurrent 1 Forward Pickup
7286
Neutral Directional Overcurrent 1 Reverse Limit Angle
7287
Neutral Directional Overcurrent 1 Reverse Pickup
7288
Neutral Directional Overcurrent 1 Target
7289
Neutral Directional Overcurrent 1 Block
728A
Neutral Directional Overcurrent 1 Events
728B
Neutral Directional Overcurrent 1 Polarizing Voltage
728C
Neutral Directional Overcurrent 1 Op Current
728D
Neutral Directional Overcurrent 1 Offset
728E
Neutral Directional Overcurrent 1 Pos Seq Restraint
728F
Reserved
7290
...Repeated for Neutral Directional Overcurrent 2
Breaker Arcing Current Settings (Read/Write Setting) (2 modules)
72C0
Breaker 1 Arcing Current Function
72C1
Breaker 1 Arcing Current Source
72C2
Breaker 1 Arcing Current Initiate A
72C3
Breaker 1 Arcing Current Initiate B
72C4
Breaker 1 Arcing Current Initiate C
72C5
Breaker 1 Arcing Current Delay
72C6
Breaker 1 Arcing Current Limit
B-28
Courtesy of NationalSwitchgear.com
RANGE
0 to 3
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 1
0 to 1
0 to 5
0 to 3
0 to 600
0 to 600
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 65535
0 to 359
0 to 3
0 to 1
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 2
-90 to 90
40 to 90
0.002 to 30
40 to 90
0.002 to 30
0 to 2
0 to 65535
0 to 1
0 to 1
0 to 1
0 to 250
0 to 0.5
0 to 1
0 to 1
0 to 5
0 to 65535
0 to 65535
0 to 65535
0 to 65.535
0 to 50000
T60 Transformer Management Relay
UNITS
STEP
FORMAT
pu
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F186
0 (Phase to Ground)
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
---
1
F300
---
1
F001
pu
0.001
F001
---
1
F126
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
---
1
F230
° Lag
1
F002
degrees
1
F001
pu
0.001
F001
degrees
1
F001
pu
0.001
F001
---
1
F109
---
1
F300
---
1
F102
---
1
F231
---
1
F196
ohms
0.01
F001
---
0.001
F001
---
1
F001
---
1
F102
---
1
F167
---
1
F300
---
1
F300
---
1
F300
s
0.001
F001
2
kA
-cyc
1
F001
APPENDIX B
DEFAULT
100
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
1000
100
100
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
0
30
700
0 (No)
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
0 (Voltage)
75
90
50
90
50
0 (Self-reset)
0
0 (Disabled)
0 (Calculated V0)
0 (Calculated 3I0)
0
63
0
0 (Disabled)
0 (SRC 1)
0
0
0
0
1000