5 SETTINGS
To set up a T60 to receive a configurable GOOSE dataset that contains two IEC 61850 single point status indications, the
following dataset items can be selected (for example, for configurable GOOSE dataset 1): "GGIO3.ST.Ind1.stVal" and
"GGIO3.ST.Ind2.stVal". The T60 will then create a dataset containing these two data items. The Boolean status values from
these data items can be utilized as remote input FlexLogic™ operands. First, the
must be set to contain dataset "GOOSEIn 1" (that is, the first configurable dataset). Then
must be set to "Dataset Item 1" and "Dataset Item 2". These remote input FlexLogic™ operands will then change state in
accordance with the status values of the data items in the configured dataset.
Floating point analog values originating from MMXU logical nodes may be included in GOOSE datasets. Deadband (non-
instantaneous) values can be transmitted. Received values are used to populate the GGIO3.XM.AnIn1... items. Received
values are also available as FlexAnalog parameters (GOOSE Analog In1...).
The main menu for the IEC 61850 server configuration is shown below.
PATH: SETTINGS
PRODUCT SETUP
SERVER
CONFIGURATION
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The
and
IED NAME
LD INST
nodes are located. Valid characters for these values are upper and lowercase letters, numbers, and the underscore (_)
character, and the first character in the string must be a letter. This conforms to the IEC 61850 standard. The
variable string and can be composed of ASCII characters. This string appears within the PhyName of the LPHD node.
The
IEC/MMS TCP PORT NUMBER
setting determines whether or not the "UR" MMS domain will be available. This domain contains a large num-
NON-IEC DATA
ber of UR-series specific data items that are not available in the IEC 61850 logical nodes. This data does not follow the IEC
61850 naming conventions. For communications schemes that strictly follow the IEC 61850 standard, this setting should be
"Disabled".
The
SERVER SCANNING
61850 has two modes of functionality: GOOSE/GSSE inter-device communication and client/server communication. If the
GOOSE/GSSE functionality is required without the IEC 61850 client server feature, then server scanning can be disabled
to increase CPU resources. When server scanning is disabled, there will be not updated to the IEC 61850 logical node sta-
tus values in the T60. Clients will still be able to connect to the server (T60 relay), but most data values will not be updated.
This setting does not affect GOOSE/GSSE operation.
Changes to the
NOTE
GE Multilin
Courtesy of NationalSwitchgear.com
COMMUNICATIONS
IED NAME: IECDevice
LD INST: LDInst
LOCATION: Location
IEC/MMS TCP PORT
NUMBER:
INCLUDE NON-IEC
DATA: Enabled
SERVER SCANNING:
Disabled
settings represent the MMS domain name (IEC 61850 logical device) where all IEC/MMS logical
setting allows the user to change the TCP port number for MMS connections. The
feature should be set to "Disabled" when IEC 61850 client/server functionality is not required. IEC
setting,
setting, and GOOSE dataset will not take effect until the T60 is restarted.
IED NAME
LD INST
T60 Transformer Management Relay
REMOTE DEVICE 1(16) DATASET
IEC 61850 PROTOCOL
Range: up to 32 alphanumeric characters
Range: up to 32 alphanumeric characters
Range: up to 80 alphanumeric characters
Range: 1 to 65535 in steps of 1
102
Range: Disabled, Enabled
Range: Disabled, Enabled
5.2 PRODUCT SETUP
setting
settings
REMOTE IN 1(16) ITEM
SERVER CONFIGURATION
LOCATION
INCLUDE
5
is a
5-21